| How the duct is formed | A strip of sheet metal is wound into a spiral tube. Its edges engage in a continuous locking seam that holds the tube together. | Check that the seam is consistently formed, without gaps, sharp protrusions, or visible damage. | Choose a duct with a sound, even seam suited to the expected handling and operating conditions. A locked seam does not automatically make the duct airtight. |
| Duct diameter | The internal diameter affects airflow area and the air velocity needed to deliver a given airflow. | Confirm the required airflow, available space, connection size, and acceptable pressure loss. | Match the duct diameter to the system design and connected equipment. Avoid selecting a size solely because it fits the available opening. |
| Metal material | Common options include galvanized steel, aluminum, and stainless steel. Material affects weight, corrosion resistance, and temperature suitability. | Consider moisture, corrosive exposure, temperature, mechanical wear, and applicable project requirements. | Use galvanized steel for many general-purpose applications, aluminum where lower weight is useful, and stainless steel where the environment requires greater corrosion resistance. Verify the grade and suitability for the specific service. |
| Wall thickness and rigidity | The metal strip forms the duct wall; its thickness and construction influence stiffness, durability, and resistance to deformation. | Check product specifications against handling loads, support spacing, operating pressure, and installation conditions. | Do not assume that all ducts of the same diameter have the same strength. Select thickness and construction using the supplier’s technical data and the system design. |
| Airflow and pressure | The duct conveys air; friction at the wall and losses at bends, transitions, and connections affect system performance. | Confirm the intended airflow direction, operating pressure, duct length, fittings, and any fan or equipment limits. | Use pressure-loss data for the actual duct and layout where available. Do not infer a pressure rating from the self-locking seam alone. |
| Leakage and sealing | The spiral seam is a mechanical interlock. Airtightness depends on duct construction, joints, fittings, and any sealing method used. | Check the required leakage class or project specification, as well as the connection and sealing details. | For applications with defined leakage requirements, select a product tested or specified for those requirements and seal joints as directed by the system design. |
| Flexibility and installation route | Wound metal ducting can follow a curved route to a degree, but it is not equivalent to a flexible fabric or foil duct. | Review bend radius, obstructions, support locations, access for maintenance, and the manufacturer’s installation guidance. | Plan smooth bends and suitable supports. Avoid crushing, kinking, or forcing the duct into a tight turn, which can restrict airflow or damage the wall and seam. |
| Connections and accessories | Compatible collars, couplings, clamps, or other fittings connect the duct to equipment and adjoining duct sections. | Confirm that connection dimensions and materials are compatible and that joints can be secured and sealed as required. | Specify connection details along with the duct. A well-made duct can still perform poorly if its joints are loose, misaligned, or inadequately sealed. |
| Operating environment | Temperature, humidity, contaminants, outdoor exposure, and cleaning methods can affect material life and suitability. | Check the product’s documented temperature limits and compatibility with the conveyed air and surrounding environment. | Choose materials and protective measures for the actual service conditions. Request technical documentation when exposure or temperature is outside ordinary indoor ventilation use. |
| Final specification check | A suitable choice balances airflow, dimensions, material, mechanical needs, installation constraints, and applicable requirements. | Confirm diameter, material, thickness, length, connection type, performance data, and any required test or compliance documentation. | Compare complete specifications rather than price or appearance alone, and verify that the selected duct is suitable for the project before ordering. |